ADM-24 Datasheet(Fiches technique) 1 Page - Gamewell-FCI by Honeywell

Numéro de pièce ADM-24
Description  Fire Alarm Control Panel with built-in DACT and remote-site upload/download capability
Télécharger  4 Pages
Scroll/Zoom Zoom In 100% Zoom Out
Fabricant  GAMEWELL-FCI [Gamewell-FCI by Honeywell]
Site Internet  http://www.gamewell-fci.com
Logo GAMEWELL-FCI - Gamewell-FCI by Honeywell

ADM-24 Datasheet(HTML) 1 Page - Gamewell-FCI by Honeywell

  ADM-24 Datasheet HTML 1Page - Gamewell-FCI by Honeywell ADM-24 Datenblatt HTML 2Page - Gamewell-FCI by Honeywell ADM-24 Datenblatt HTML 3Page - Gamewell-FCI by Honeywell ADM-24 Datenblatt HTML 4Page - Gamewell-FCI by Honeywell  
Zoom Inzoom in Zoom Outzoom out
 1 / 4 page
background image
Flex 405
CS-2405 09/01/06
Page 1 of 4
Description
The Gamewell Flex 405 is a 24-volt,
five-zone Fire Alarm Control Panel
FACP) with built-in communicator and
remote-site upload/download capabil-
ity. The integral communicator trans-
mits event information (alarms,
troubles, supervisories, faults, etc.) to
a UL-Listed central station. The Flex
405 may be used in a variety of cost-
effective applications, including: local
fire alarm control panel (communica-
tor disabled), fire alarm control panel/
communicator, stand-alone sprinkler
supervisory communicator, or slave
communicator to a UL-Listed host fire
alarm panel (requires normally-open dry
contacts to trigger five channels). Selectable transmission formats allow the
Flex 405 to communicate to virtually all central stations.
Remote-Site Upload/Download
The Flex 405 may be downloaded or uploaded without affecting the system fire
protection. Download system programming, and upload key system information
such as: current system status, history and walk test files; zone, AC line, NAC
1 and NAC 2, resettable power and battery voltages; and system programming.
Upload or download within one minute without affecting normal fire panel func-
tions. The upload/download function also features multiple security techniques.
The Flex 405 requires the PK-CD programming kit, which works with most Hayes-
compatible modems (consult factory for listing).
Features
? Five programmable Initiating Device Circuits
(zones). Each zone may be programmed for:
two-wire smoke detectors, normally open
contact devices (pull stations, heat detectors),
four-wire smoke detectors, waterflow
operation, supervisory operation, auto-reset
supervisory operation.
? Two built-in, Class A or B (Style Z or Y)
Notification Appliance Circuits (NACs).
NACs may be programmed: silenceable,
non-silenceable (a strobe circuit can keep
flashing after the panel is silenced), auto-
silence (program 5 to 30 minutes), silence
inhibit (60 seconds), coding (march time,
temporal, California).
? 3.0 amps of notification appliance power,
expandable to 5.0 amps (meets the critical
power requirements for ADA and UL-1971
devices).
? Two built-in Form-CAlarm andTrouble relays.
? Supervisory and communication fail outputs.
? Dual-line rotary- or Touch-Tone-dial DACT
interfaces to public telephone network (leased
phone lines are not required).
? 24-Volt operation.
? Built-in voltmeter measures: zone voltage;
primary AC line voltage; battery voltage;
NAC(s) voltage; resettable 24-volt power.
? Surface Mount Technology (SMT).
? Fully programmable via built-in keypad (no
costly external programmers necessary).
? Complies with NFPA 72 (Local, Central
Station and Remote Station [DACT only ? not
polarity reversal] Fire Alarm Systems).
? Reporting formats include:
3+1, 4+1, 4+2 Standard + Expanded;
4+1, 4+2, Ademco Express.
? Integral battery charger for up to 60 hours of
standby power.
? Fuseless, power-limited technology meets
UL power-limiting requirements.
? Programmable alarm presignal timer, alarm
verification timer, and optional trouble
reminder.
? Single-person walk test. Fire drill function.
? Zone disable capability (software).
? 32-Event history buffer with time-and-date
stamp.Accurate real-time clock/calendar.
? Extensive built-in transient protection.
? Electronics and operational controls fully
enclosed in a lockable cabinet capable of
housing up to 7 AH batteries.
? Optional: contact-by-zone module, remote
annunciator, printer interface for on- or off-line
printing.
Listings
Listings and approvals below apply to the
basic Flex 405 panel. In some cases, certain
modules may not be listed by certain
approval agencies, or listing may be in
process. Consult factory for latest listing
status.
? UL Listed.
? CSFM approved: file 7165-1288:179.
? MEA approved: file 366-04-E.
Flex 405
Fire Alarm Control Panel with built-in DACT
and remote-site upload/download capability


Html Pages

1  2  3  4 


Datasheet Download

Go To PDF Page


Lien URL



Privacy Policy
ALLDATASHEET.FR
AllDATASHEET vous a-t-il été utile ?   [ DONATE ]  

propos de Alldatasheet   |   Publicit   |   Contactez-nous   |   Politique de confidentialit   |   Echange de liens   |   Manufacturer List
All Rights Reserved Alldatasheet.com


Mirror Sites
English : Alldatasheet.com  |   English : Alldatasheet.net  |   Chinese : Alldatasheetcn.com  |   German : Alldatasheetde.com  |   Japanese : Alldatasheet.jp
Russian : Alldatasheetru.com  |   Korean : Alldatasheet.co.kr  |   Spanish : Alldatasheet.es  |   French : Alldatasheet.fr  |   Italian : Alldatasheetit.com
Portuguese : Alldatasheetpt.com  |   Polish : Alldatasheet.pl  |   Vietnamese : Alldatasheet.vn